H12

Malfunction Decision Conditions

  • During startup, error code appears when different types of indoor and outdoor units are interconnected.

Malfunction Caused

  • Wrong models interconnected.
  • Wrong indoor unit or outdoor unit PCBs mounted.
  • Indoor unit or outdoor unit PCBs defective.
  • Indoor-outdoor unit signal transmission error due to wrong wiring.
  • Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor units.

Troubleshooting

When abnormality indication starts again
Check the indoor and outdoor unit connection wires
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Is there any wiring error?
YES
Correct the indoor-outdoor units connection wires
NO
Check indoor and outdoor units model number.
Is indoor unit and outdoor unit model numbers matched?
NO
Match the compatible model(s)
YES
Check the spare part numbers of the indoor and outdoor unit PCBs and compare with their Part Lists
YES
Matched compatibility?
NO
Change for the specified indoor or outdoor unit PCB
Replace the indoor and outdoor unit PCBs