H24

Malfunction Decision Conditions

  • During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors.

Malfunction Caused

  • Faulty connector connection.
  • Faulty sensor.
  • Faulty PCB.

Troubleshooting

When abnormality indication starts again
Check the connector connection:
• Plug out connector from the indoor unit PCB
• Measure the resistance of the indoor pipe temperature sensor
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Is the connector connection normal?
NO
  • Connector poor contact
  • Correct the connection
YES
Check the indoor air temperature sensor:
• Plug out connector from the indoor unit PCB
• Measure the resistance of the indoor intake air temperature sensor
Is the measured resistance of the indoor intake air temperature sensor matches the value specified in its characteristic chart?
NO
  • Defect in indoor intake air temperature sensor
  • Replace the indoor intake air temperature sensor
YES
YES
  • Defect in indoor unit PCB
  • Replace the indoor unit PCB