During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
↓
Check the connector connection:
• Turn off the power
• Check the connector connection
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
↓
Is the connector connection normal?
NO →
Connector poor contact
Correct the connection
YES
↓
Check the outdoor discharge pipe temperature sensor:
• Plug out connector from the outdoor unit PCB
• Measure the resistance of the outdoor discharge pipe temperature sensor
↓
Is the measured resistance of the outdoor gas pipe temperature sensor matches the value specified in its characteristic chart?
NO →
Defect in outdoor discharge pipe temperature sensor
Replace the outdoor discharge pipe temperature sensor