H98

Malfunction Decision Conditions

  • Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation.
  • Phenomena: unit is stopping and re-starting very often in heating mode

Malfunction Caused

  • Indoor heat exchanger thermistor
  • Clogged air filter or heat exchanger
  • Over-bent pipe (liquid side)

Troubleshooting

When abnormality indication starts again
Check the indoor unit intake air filter
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Is the air filter dirty?
YES
  • Clean the air filter
NO
Check the dust accumulation on the indoor unit heat exchanger
Is the indoor unit heat exchanger dirty?
YES
  • Clean the indoor unit heat exchanger
NO
Check the indoor pipe temperature thermistor:
• Plug out connector (CN-TH) from the indoor unit PCB
• Measure the resistance of the indoor heat exchanger temperature thermistor
Is the measured resistance of the indoor pipe temperature thermistor matches the value specified in its characteristic chart?
NO
  • Defect in indoor pipe temperature thermistor
  • Replace the indoor pipe temperature thermistor
YES
YES
  • Check the piping & installation condition
  • Replace piping / reinstall the unit if necessary