H99

Malfunction Decision Conditions

  • Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)

Malfunction Caused

  • Air short circuit at indoor unit
  • Clogged indoor unit air filter
  • Dust accumulation on the indoor unit heat exchanger
  • 2/3 way valve closed
  • Faulty indoor unit fan motor
  • Refrigerant shortage (refrigerant leakage)
  • Clogged expansion valve or strainer
  • Faulty indoor pipe temperature sensor
  • Faulty indoor unit PCB

Troubleshooting

When abnormality indication starts again
Check the air passage
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Is there any short circuit?
YES
  • Provide sufficient air passage
Check the indoor unit air filter
Is the air filter dirty?
YES
  • Clean the air filter
NO
Check the dust accumulation on the indoor unit heat exchanger
Is the indoor unit heat exchanger dirty?
YES
  • Clean the indoor unit heat exchanger
NO
Check if 2/3 way valve is closed?
YES
  • Open the 2/3 way valve.
NO
Check if indoor fan motor operates normally?
NO
  • Replace the indoor unit fan motor and/or indoor unit PCB.
YES
Check for gas leakage. Is Oil oozing out from the 2/3 way valve?
YES
  • Repair the pipe flare or union nuts
  • Reclaim and recharge refrigerant
Check if expansion valve or strainer clogged (ice formed)?
YES
  • Reclaim and recharge with correct amount of refrigerant.
NO
Check the indoor pipe temperature sensor
Does it conform to the sensor characteristic chart?
NO
  • Replace the indoor pipe temperature sensor
YES
YES
  • Replace the indoor unit PCB