A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit.
Malfunction Caused
Compressor terminal disconnect
Faulty Outdoor PCB
Faulty compressor
Troubleshooting
When F93 indication happens
⚠
Caution
For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
↓
Check the U, V and W connector connection:
- Turn OFF the power
- Check the U, V and W connector connection at outdoor PCB and compressor terminal
↓
Is the connector connection normal?
NO →
Connector poor contact
Correct the connection
YES
↓
Disconnect the harnesses U, V and W from the compressor terminal
↓
From the disconnected harnesses U, V and W, connect them to the inverter checker. Turn ON the power and operate the system. Check the inverter checker 6 LEDs blinking condition.
↓
Is the blinking of the 6 LEDs in same sequence/condition?