F97

Malfunction Decision Conditions

  • During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the compressor tank temperature sensor.

Malfunction Caused

  • Faulty compressor tank temperature sensor
  • 2/3 way valve closed
  • Refrigerant shortage (refrigerant leakage)
  • Faulty outdoor unit PCB
  • Faulty compressor

Troubleshooting

When F97 indication happens
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Check the compressor tank temperature sensor.
Does it conform to the sensor characteristic chart?
NO
  • Replace the compressor tank temperature sensor.
YES
2/3 way valve closed?
YES
  • Open the 2/3 way valve.
NO
Check for gas leakage.
Oil oozing out from the 2/3 way valve?
YES
  • Repair the pipe flare or union nuts.
  • Reclaim and recharge refrigerant.
NO
Check if expansion valve or strainer clogged (ice formed)
YES
  • Replace expansion valve and/or strainer
  • Reclaim and recharge refrigerant
NO
Reclaim and recharge for a specified amount of fresh refrigerant
Refrigerant cycle abnormality error again?
YES
  • Replace outdoor unit PCB
  • Replace outdoor unit compressor
NO
NO
  • Procedure complete