(ECOi-Geräte)
Alarm Code | L10 | |||
---|---|---|---|---|
Alarm meaning | Outdoor unit capacity not set | |||
Alarm conditions | The outdoor unit capacity has not been set, or the setting is not allowed by the system. | |||
Probable cause | This alarm occurs because the capacity has not been set. | |||
Check | If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it correctly. * After changing the setting, be sure to reset both the indoor and outdoor power. | |||
Correction |
|
|||
Example | – | |||
Notes | The outdoor unit maintenance remote controller is required in order to set the capacity in the outdoor unit EEPROM. |