(ECOi-Geräte)
Alarm Code | H07 | |||
---|---|---|---|---|
Alarm meaning | No-oil alarm | |||
Alarm conditions |
This alarm occurs when oil does not flow for a specified amount of time in tubing where oil flow constantly. (The presence of oil is detected by a temperature sensor.) Judgment method: Tcal={(0.0254 · T_oil · LP2 +0.0298 · T_oil · LP +0.8842 · T_oil –2.9953 · LP2 –11.091 · LP +436.94) +2.9953 · HP2 +11.091 · HP –436.94}/(0.0254 · HP2 +0.0298 · HP +0.8842) |
|||
Probable cause |
Insufficient amount of oil in the system
|
|||
Check |
|
|||
Correction |
|
|||
Example | – | |||
Notes | – |