F91

Malfunction Decision Conditions

  • The input current is low while the compressor is running at higher than the setting frequency.

Malfunction Caused

  • Lack of gas.
  • 3-way valve close.

Troubleshooting

When F91 indication happens
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Check 3 way valve
3-way valve opened?
NO, closed
  • Open 3 way valve
YES
Check for gas leaking source (Refer to H16)
Gas leaking?
YES
  • Check for gas leaking source;
    Repair or replace defected part(s)
  • Re-claim and then re-charge the right amount
NO, gas amount is OK
Check other parts in refrigeration cycles