H14

Malfunction Decision Conditions

  • During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors.

Malfunction Caused

  • Faulty connector connection.
  • Faulty sensor.
  • Faulty PCB.

Troubleshooting

When abnormality indication starts again
Check the connector connection:
• Turn off the power
• Check the connector connection
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Is the connector connection normal?
NO
  • Connector poor contact
  • Correct the connection
YES
Check the indoor intake air temperature sensor:
• Plug out connector from the indoor unit PCB
• Measure the resistance of the indoor intake air temperature sensor
Is the measured resistance of the indoor intake air temperature sensor matches the value specified in its characteristic chart?
NO
  • Defect in indoor intake air temperature sensor
  • Replace the indoor intake air temperature sensor
YES
YES
  • Defect in indoor unit PCB
  • Replace the indoor unit PCB