H19

Malfunction Decision Conditions

  • The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm)

Malfunction Caused

  • Operation stops due to short circuit inside the fan motor winding.
  • Operation stops due to breaking of wire inside the fan motor.
  • Operation stops due to breaking of fan motor lead wires.
  • Operation stops due to Hall IC malfunction.
  • Operation error due to faulty indoor unit PCB.

Troubleshooting

When abnormality indication starts again
Turn off power supply and rotate fan by hand
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Does fan rotate smoothly?
NO
  • Replace fan motor
YES
Turn power supply on and operate fan.
Does it rotate?
YES
Stop fan motor
NO
If fan does NOT rotate:
Turn off power supply and disconnect fan motor connector, then turn power on.
Check the output of fan motor from indoor PCB
Is the motor power supply voltage ~325Vdc (pin 1 & 4) generated?
NO
NO →↓ (Go to Replace indoor PCB)
Is the motor control voltage 15Vdc (pin 5 & 4) generated?
NO
NO →↓ (Go to Replace indoor PCB)
Operate the fan, is the rotation command voltage 1~5Vdc (pin 6 & 4) generated?
NO
NO →↓ (Go to Replace indoor PCB)
YES
YES
If fan rotates (from Stop fan motor):
Check the rotation feedback output from fan motor.
Rotate the fan motor by hand, is the rotation feedback voltage 15Vdc (pin 7 & 4) generated?
NO
YES
YES
  • Replace indoor PCB
NO (from Rotate check) / YES (from Rotate command)
  • Replace fan motor