H85

Malfunction Decision Conditions

  • Initial Setting: Main PCB does not receive WLAN module data for 90 secs.
  • Normal Control: Main PCB does not receive WLAN module data for 10 mins repeating 2 times.
    • 5V power to WLAN module is turned off for 2s.
    • After 2s, 5V power to WLAN module is turned on & start initial setting.
    • WLAN LED Off & Timer LED blinking.

Malfunction Caused

  • Faulty lead wire connector connection.
  • Faulty indoor unit PCB.
  • Faulty WLAN module.

Troubleshooting

When abnormality indication starts again.
Caution For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.
Turn ON WLAN function. 5V supplied to WLAN module?
(Pin 1 & Pin 8)
NO
  • Replace main PCB.
YES
  • Connector plug in properly.
    Check WLAN module lead wire continuity
NO
  • Properly plug in connector.
    Change the lead wire.
  • Replace WLAN module.
  • Comfort Cloud operation normal and WLAN LED is ON?
NO
  • Change the main PCB.