Störungscode F06_F23_F25_ECOi_MF1
(ECOi-Geräte)
Warning: Undefined variable $maxsuche in
/home/.sites/site1/wwwroot/web/includes/Codedetail.php on line
36
Alarm Code | F06, F23, F25 |
Alarm meaning |
Gas temperature sensor trouble at outdoor heat exchanger 1; Gas temperature sensor trouble at outdoor heat exchanger 2; Gas temperature sensor trouble at outdoor heat exchanger 3 |
Alarm conditions |
- A/D step is 10 steps or less (short circuit).
- A/D step is 1014 steps or more (open circuit).
|
Probable cause |
- Sensor malfunction (including connector)
- PCB malfunction
|
Check |
- Measure the sensor resistance. Check that the sensor is operating normally.
- Use a remote controller monitor or PC monitor to check the temperature that is recognized by the microcomputer.
|
Correction |
– |
Example |
– |
Notes |
– |