Error in Indoor Unit Transmitting Signal to Remote Controller
1. Error Detection Method
It is judged an error when an indoor unit cannot itself receive a signal that it sent to its remote controller(s).
- Indoor unit control PC board faulty
- The remote control´s wires 1(white) and 2(black) are shorted or opened.
1 Indoor unit control PCB |
1-1 |
Are the remote control´s wires 1(white) and 2(black) are shorted or opened? |
Yes |
Correct the wiring |
No |
1-2 |
1-2 |
Replace the indoor unit control PC board. |
- For information on the procedures for replacing the Indoor unit control PC board, refer to the manual that is packaged with theindoor unit service board.