Störungscode E13_Mini_ECOi

(ECOi-Geräte)


Warning: Undefined variable $maxsuche in /home/.sites/site1/wwwroot/web/includes/Codedetail.php on line 36

Error in Indoor Unit Transmitting Signal to Remote Controller

1. Error Detection Method

It is judged an error when an indoor unit cannot itself receive a signal that it sent to its remote controller(s).

  • Indoor unit control PC board faulty
  • The remote control´s wires 1(white) and 2(black) are shorted or opened.

2. Error Diagnosis

1
Indoor unit control PCB 
1-1 Are the remote control´s wires 1(white) and 2(black) are shorted or opened? Yes Correct the wiring
No 1-2
1-2 Replace the indoor unit control PC board.

 

  • For information on the procedures for replacing the Indoor unit control PC board, refer to the manual that is packaged with theindoor unit service board.