(ECOi-Geräte)
| Alarm Code | E12 | |||
|---|---|---|---|---|
| Alarm meaning | Automatic address setting start is prohibited. | |||
| Alarm conditions | Automatic address setting was started when automatic address setting was in progress at another outdoor unit in the same link. | |||
| Probable cause |
Automatic address setting is in progress at another outdoor unit. |
|||
| Check | This alarm is not displayed on the remote controller. Therefore check the blinking on the outdoor unit PCB. | |||
| Correction | Then start automatic address setting again. Wait for automatic address setting to be completed at the outdoor unit where it is currently in progress. | |||
| Example | – | |||
| Notes | – | |||