(ECOi-Geräte)
Alarm Code | E25 | |||
---|---|---|---|---|
Alarm meaning | Outdoor unit address setting failure (duplication) | |||
Alarm conditions | Communication by outdoor unit main-sub control wiring was received that contained the same address as that unit 5 times or more within 3 minutes. | |||
Probable cause | The unit number is set incorrectly. | |||
Check | Check the unit number again. | |||
Correction | – | |||
Example | – | |||
Notes | Recovery from this alarm occurs automatically (when communication that contains the same address is not received for 3 minutes). |