(ECOi-Geräte)
Alarm Code | L04 | |||
---|---|---|---|---|
Alarm meaning | Outdoor system address duplication | |||
Alarm conditions | Communication by inter-unit control wiring was received that contained the same address as that unit 5 times or more within 3 minutes. | |||
Probable cause | Incorrect outdoor system address settings | |||
Check |
Check the system address settings again. |
|||
Correction | Correct the system address settings. | |||
Example | – | |||
Notes | Recovery from this alarm occurs automatically (when communication that contains the same address as that unit is not received for 3 minutes after detection). |