Panasonic ProClub

Impressum Datenschutz Volltextsuche Kunden-Login

 

Störungscode P16_ECOi_MF1

(ECOi-Geräte)

 

Alarm Code P16
Alarm meaning Compressor 1 (INV) overcurrent alarm
Alarm conditions This alarm occurs when current trouble or current detection trouble occur at an inverter frequency of less than 80 Hz after start (when trouble judgment current is detected in the primary or secondary current, or when an instantaneous secondary current of 48 A or higher is detected. 
Probable cause There is a strong possibility of a compressor failure.
An alarm occurs for current detection trouble when it is judged that no current is flowing after start (DCCT is damaged). In this case, the cause is a DCCT failure.
Check Check the power wiring and connector wiring.
Correction It is possible to resolve this trouble by limiting the maximum frequency.
Example
Notes

 

 

 


 

 

Website durchsuchen ...

 

 


Kunden-Login