(ECOi-Geräte)
| Alarm Code | E25 | |||
|---|---|---|---|---|
| Alarm meaning | Outdoor unit address setting failure (duplication). | |||
| Alarm conditions | Communication by outdoor unit main-sub control wiring was received that contained the same address as that unit 5 times or more within 3 minutes. | |||
| Probable cause | The unit number is set incorrectly. | |||
| Check | Check the unit number again. | |||
| Correction | – | |||
| Example | – | |||
| Notes | Recovery from this alarm occurs automatically (when communication that contains the same address is not received for 3 minutes). | |||