(ECOi-Geräte)
| Alarm Code | F16 | |||
|---|---|---|---|---|
| Alarm meaning | High-pressure sensor trouble (abnormal rise in high pressure) (In some cases this may not be the result of a high-pressure sensor malfunction.) | |||
| Alarm conditions |
|
|||
| Probable cause |
|
|||
| Check |
1. High-pressure sensor failure
2. Failure to open the service valve, clogged tubing, valve leakage, over-charging.
3. Outdoor unit PCB failure
|
|||
| Correction |
1. Replace the high-pressure sensor. Because the high-pressure sensor connection employs a Schrader-type valve, it can be removed and replaced. However, the high-pressure sensor can be easily damaged by high voltage; therefore use sufficient caution with regard to static electricity. 2. Replace the PCB. 3. Correct the locations of problems in the refrigeration cycle.
During cooling: During heating: |
|||
| Example | This alarm may result when the service valve is closed or when valve leakage (particularly from the mechanical valve) occurs. | |||
| Notes | – | |||