| Alarm Code | L04 | |||
|---|---|---|---|---|
| Alarm meaning | Outdoor system address duplication | |||
| Alarm conditions | Communication by inter-unit control wiring was received that contained the same address as that unit 5 times or more within 3 minutes. | |||
| Probable cause | Incorrect outdoor system address settings | |||
| Check | Check the system address settings again. | |||
| Correction | Correct the system address settings. | |||
| Example | – | |||
| Notes | Recovery from this alarm occurs automatically (when communication that contains the same address as that unit is not received for 3 minutes after detection). | |||