(ECOi-Geräte)
| Alarm Code | L18 | |||
|---|---|---|---|---|
| Alarm meaning | 4-way valve operation failure | |||
| Alarm conditions | During heating operation (Comp. ON), the highest detected temperature at an outdoor unit heat exchanger (EXG 1, EXG 2, EXL 1, or EXL 2) was 20°C or more above the outdoor air temperature (Air Temp.) continuously for 5 minutes or longer, or the detected suction temperature (SCT) was 20°C or more above the outdoor air temperature continuously for 5 minutes or longer. | |||
| Probable cause |
|
|||
| Check |
|
|||
| Correction | If the connector is normal, correct or replace the problem locations. | |||
| Example | – | |||
| Notes | – | |||