(ECOi-Geräte)
| Alarm Code | P04 | |||
|---|---|---|---|---|
| Alarm meaning | High-pressure switch activated. | |||
| Alarm conditions | The operation of the electronic circuit in the high-pressure switch may short-circuit the terminal depending on the pressure. A pressure of 3.3 MPa or above will short-circuit the terminal. Once the terminal is short-circuited, it will remain in that state until the pressure goes below 2.6 MPa. | |||
| Probable cause |
|
|||
| Check |
|
|||
| Correction | Replace damaged components and correct the amount of charged refrigerant. | |||
| Example | – | |||
| Notes | – | |||