Alarm Code
P14
Alarm meaning
O2 sensor operation
Alarm conditions
It is judged an error whenever the outdoor unit receives the signal O2 Alarm Generated from the indoor unit.
With the indoor unit´s EEPROM setting (item code 0B) set to 0001, the EXCT input was shorted.
Probable cause
–
Check and Correction
System configuration 1-1 Is an O2 sensor being used? If Yes, see 3-1. If No, see 2-1.
2-1 Indoor EEPROM setting Is the EEPROM setting, item code 0B, on the indoor control board set to 0001? If Yes, see 3-1 after modification. If No, see 4-1.
3-1 EXCT wiring Is the EXCTsocket (wire) shorted? If Yes, Modify the wiring. If No, see 4-1.
Indoor control board 4-1 Is the alarm triggered if the EXCT socket (wire) is disconnected, and the power is reset? If Yes, see 4-3. If No, see 4-2.
4-2 Since there is no error, see what happens.
4-3 Indoor control board defective → replace board