(ECOi-Geräte)
| Alarm Code | P22 | |||
|---|---|---|---|---|
| Alarm meaning | Fan motor trouble. | |||
| Alarm conditions | Fan motor start failure, fan motor Hall IC input failure. | |||
| Probable cause | Possible causes are a Hall IC input circuit failure and a fan HIC failure. | |||
| Check |
Check the fan motor wiring, the Hall IC wiring, and the connector connections.
|
|||
| Correction |
If the fan does not start, the below corrections may be effective.
|
|||
| Example | – | |||
| Notes | Turn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB. | |||